450 m³/h · AGRICULTURAL IRRIGATION WATER · UV COMPLETED & OPERATING

Philippines 450 m³/h Agricultural-Irrigation UV System

Philippines · Delivered and operating since 2025 · No pathogen-removal claim published

Konche (Shenzhen) Water Treatment Technology Co., Ltd. completed equipment delivery for this project, and the equipment was put into use in 2025. The 450 m³/h installed system treats surface water for agricultural irrigation in the Philippines using 30 low-pressure UV lamps, UV-intensity monitoring and automatic mechanical sleeve cleaning.

Location
Philippines; final site and customer identity withheld
Application
Surface-water treatment for agricultural irrigation
Configured flow
450 m³/h
Installed UV configuration
30 × 320 W low-pressure lamps; 9.6 kW total lamp power
Installed reactor and cleaning
316L reactor with pneumatic mechanical sleeve cleaning
Status
Delivered and operating since 2025
Stainless-steel flow-through UV reactors with multiple lamp ports in a workshop
Flow-through UV reactor configuration view; not a site-installation photograph.

How does UV water treatment work?

UV provides a physical disinfection step without adding a residual chemical to the irrigation stream. Its effectiveness depends on the target organisms, actual flow, water clarity and the minimum UV transmittance, so upstream solids control remains important.

How does UV disinfection work in water treatment?

The installed system routes water through a 316L flow-through reactor with 30 low-pressure 320 W lamps. UV-intensity monitoring, one electronic ballast per lamp and staged lamp operation support control across the operating range. The installed controls include individual-lamp alarms and an outdoor cabinet.

450 m³/h UV equipment configuration

The installed system includes a 316L reactor, 30 UV lamps, electronic ballasts, UV-intensity monitoring, PLC and operator-interface hardware. Pneumatic mechanical wiping is configured to clean the quartz sleeves without opening the reactor for every cleaning cycle.

Performance note: flow alone cannot establish UV dose or microbial reduction. For a comparable project, sizing requires minimum UVT, turbidity, suspended solids, target organisms, required reduction and a verification method.

Water data needed for UV system sizing

Provide peak and minimum flow, minimum UVT, turbidity and suspended solids, target organisms or treatment objective, upstream filtration, allowable head loss, pipe size, control interface, outdoor conditions and the verification method. UV equipment should be selected from those inputs rather than flow alone.

PROJECT INQUIRY

Size an irrigation-water UV system.

Share peak flow, minimum UVT, turbidity, suspended solids, target organisms, pipe size and control requirements.

Review Project Fit ↗