LATIN AMERICA · 10 m³/h RO COMPLETED & OPERATING · COOLING-WATER MAKEUP

Latin America 10 m³/h Cooling-Water Makeup RO System

Latin America · Delivered and operating since 2025 · 10 m³/h net RO operating duty

Konche (Shenzhen) Water Treatment Technology Co., Ltd. completed equipment delivery for this project, and the equipment was put into use in 2025. The operating system is rated for 10 m³/h net RO permeate for an open cooling-tower and condenser-loop makeup duty. Its upstream aeration and pretreatment section has a separate rated flow of 45.5 m³/h and serves a different hydraulic function.

Region
Latin America; country, customer and site withheld
Application
Cooling-tower and open condenser-loop makeup water
Feed water
Groundwater from the project well
Installed RO capacity
10 m³/h net permeate
Installed treatment train
Aeration and settling, manganese-sand filtration, activated carbon, cartridge filtration and single-pass BWRO
Status
Delivered and operating since 2025

What is makeup water in a cooling tower?

Makeup water replaces evaporation, drift and blowdown losses. Its chemistry affects scaling, corrosion and biological control, so the required treatment depends on the source water, target cycles of concentration and the cooling-water chemistry program.

Do cooling towers need water treatment?

Yes. This installed system had to address iron, silica, hardness and oil in groundwater before the water entered the cooling system. It specifies forced aeration → oxidation and settling → parallel manganese-sand filtration → activated-carbon filtration → 5 µm cartridge filtration → single-pass BWRO → product-water storage → cooling-water makeup.

Do RO systems work on well water?

RO can treat well water when the pretreatment controls the contaminants that would foul or scale the membranes. In this configuration, manganese-sand filtration supports iron removal, activated carbon addresses oil, cartridge filtration protects the RO stage, and antiscalant dosing and membrane flushing support operation.

How do you calculate makeup water for a cooling tower?

Calculate evaporation, drift and blowdown at the target cycles of concentration, then add the operating reserve and storage requirement. In this installed system, 45.5 m³/h refers to the upstream aeration and pretreatment section, while 10 m³/h is the net RO permeate duty; the two figures describe different process boundaries.

Water-quality note: the operating limits for conductivity, chloride, hardness, silica and iron are project-specific and must remain aligned with the cooling-system water-management program.